An irrigation technician turns on a pump and sees 6.2 bar at the pressure transmitter but only 3.8 bar on the control screen. The pump is running, the line is pressurized, and no alarm is triggered. The actual cause is a loose terminal that reduced the loop current from 14.8 mA to 10.4 mA. This is what a 4-20 mA signal does in practice: it translates a physical process value into a measurable electric current, and every milliampere on the loop carries meaning. Learning how the current maps to the measurement helps technicians diagnose problems faster and choose the right components for automation and irrigation systems.
A 4-20 mA signal is a controlled electrical current used to represent a physical measurement. A transmitter reads a variable such as pressure, temperature, flow rate, level, or valve position, and converts it into a current between 4 mA and 20 mA. The value of 4 mA represents the low end of the measurement range, and 20 mA represents the high end.
The conversion is linear. The formula used is:
I = 4 + [16 × (V - Vmin) / (Vmax - Vmin)]
In this formula, I is the loop current in mA, V is the physical value, and Vmin and Vmax are the limits of the measurement span. If you have a pressure range of 0 to 10 bar and the current reads 12 mA, the pressure is (12 - 4) / 16 × 10 = 5 bar. If a flow meter with a range of 0 to 100 L/s produces 14 mA, the flow is (14 - 4) / 16 × 100 = 62.5 L/s.
The current flows through a closed loop made of two wires. The transmitter controls the current, the power supply provides voltage, and the receiver, which can be a PLC, controller, or display, reads the current. Because this is a current signal and not a voltage signal, the length and resistance of the wiring do not change the reading, as long as the total loop resistance stays within the voltage from the power supply.
The 4 mA lower limit is called a live zero. A live zero means that a true zero measurement still produces 4 mA. If the loop current falls to 0 mA, the system immediately knows that the wire is broken, the transmitter is dead, or the power supply failed. If the lower limit were 0 mA, the system could not tell the difference between a genuine zero reading and a fault.
The 20 mA upper limit comes from a mix of safety, compatibility, and practical resolution requirements. Under a 24 VDC supply, a 20 mA current allows intrinsically safe operation in many hazardous areas, keeps power loss low, and provides enough span for good resolution in a typical analog input.
The 4 mA baseline also supports two-wire transmitters. A two-wire transmitter must power its own internal electronics from the same loop wires. The transmitter draws its operating current from the loop, so a 4 mA minimum leaves enough margin to keep the electronics alive while still sending a valid low-end process value.
| Process value (% of span) | Loop current (mA) | Meaning |
|---|---|---|
| 0% | 4.0 | Live zero, valid minimum |
| 25% | 8.0 | Quarter scale |
| 50% | 12.0 | Mid scale |
| 75% | 16.0 | Three-quarter scale |
| 100% | 20.0 | Full scale |
| Below 4 mA | 0 - 4.0 | Under-range or sensor fault |
| 0 mA | 0 | Open loop or dead transmitter |
A complete current loop consists of four elements:
The loop budget formula is:
V_supply = I_max × (R_wire + R_receiver + R_contacts) + V_transmitter_min
For example, with a 24 VDC supply, a 250-ohm input, 20 ohms of wiring resistance, and a transmitter that needs 10 V to operate:
V_drop = 0.020 × (250 + 20) + 10 = 15.4 V
The 24 VDC supply leaves a margin of 8.6 V. This explains why a 4-20 mA loop can run across hundreds of meters of cable without a separate signal booster.
In industrial fluid control and irrigation automation, 4-20 mA is used for measurement and control, not for direct valve actuation. A solenoid valve requires a separate power output from the controller to energize its coil. The 4-20 mA signal provides the process data that the controller needs to decide when to open or close the valve.
Typical applications include:
When you design an off-grid irrigation station, a solar valve controller that can accept a 4-20 mA input and pulse a latching actuator is a good fit. This type of controller reads a soil moisture or pressure sensor and uses the signal to decide when to open the valve without relying on grid power.
Solar-Powered LoRa Valve Controller with Dual OutputsThis controller uses solar charging and a lithium battery for off-grid operation, accepting 4-20 mA sensor inputs to pulse latching solenoids, ideal for irrigation stations without reliable power.View Product →
If the station needs stable downstream pressure, a pressure-regulating solenoid valve is the key component. The controller reads a pressure transmitter and sends a corrective signal to the valve, keeping the pressure within the required tolerance.
Pressure-Regulating Nylon Valve for Stable Downstream PressureThis valve maintains a preset downstream pressure despite upstream fluctuations, ensuring consistent flow for irrigation and municipal systems, with optional switch monitoring for remote oversight.View Product →
For flow measurement and remote monitoring, an intelligent water meter valve series gives you local readout plus a remote signal path. This is useful for project engineers who need actual irrigation volume data rather than a runtime estimate.
Water Meter Valve with Remote Transmission for Flow MonitoringCombining a plastic water meter and valve in one unit, this kit saves space and cost while enabling remote flow monitoring and control via LoRa or Bluetooth, suitable for irrigation networks.View Product →
For broader plant control, industrial two-way water valves are often combined with 4-20 mA loops in process skids, cooling systems, and greenhouse climate control. The signal path is the same: a sensor reads the process, the loop transmits the value, and the controller responds.
If you need more background on how solar-powered control fits into this, the article how solar solenoid valve controllers work explains the connection between solar power, low-power actuators, and the control signals that drive them.
When you install a loop, there are several practical items to check.
A practical troubleshooting sequence is:
Common faults and what they mean:
The most useful takeaway is to think of the loop as a single continuous current path. Every junction, terminal, and wire segment is part of the measurement. Verifying the current at the receiver proves what the controller is seeing, but verifying it at the transmitter proves what the process is actually doing.
A well-designed 4-20 mA loop is a dependable way to connect sensors and controllers over long distances. It remains popular because of its live-zero self-check, immunity to voltage drops, and broad compatibility with industrial automation hardware. In irrigation and valve control, the same standard is used to keep water pressure stable, report flow accurately, and automate field operations with minimal energy.
Understanding the Role of an Irrigation Solenoid Valve in Modern Sprinkler Systems Irrigation systems have evolved significantly over the years, moving from basic manual systems to...
READ MOREIntroduction to Solenoid Actuators What is a Solenoid Actuator? A solenoid actuator is an electromechanical device that converts electrical energy into mechanical motion through th...
READ MOREIntroduction to KGF Irrigation Solenoid Valves Brief Overview of KGF irrigation solenoid valves as a Brand and Their Presence in the Irrigation Industry KGF irrigation solenoid val...
READ MOREA plastic water meter is a device made from durable, corrosion-resistant plastic polymers that is used to measure the volume of water flowing through a pipeline. Unlike traditional...
READ MOREHehua Bridge, Yunlong town, Yinzhou district, Ningbo city
+86 18957812511
seven@irririchvalve.com
Copyright © NINGBO IRRIRICH WATER-SAVING TECHNOLOGY CO.,LTD.All Rights Reserved